Brand Name : CITY
Model Number : 4P-90 4P-90C PM143-000
Place of Origin : Britain
MOQ : 1
Payment Terms : L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability : 311/pcs/pre
Delivery Time : 3-5work days
Packaging Details : canned
Gases Detected : Most combustible gases and vapours
Range : 0-100% LEL
Operating Voltage : 3.30V d.c.
Detector Operating : 74±6mA
Poison Resistance : Resistant to H2S poisoning
Product Description:
4P-90 4P-90C PM143-000 Combustible Gas sensor For Catalytic Combustion
Features:
The table below shows the variation in response of a 4P-
90 CiTipeL on exposure to a range of gases and vapours
at the same %LEL concentration. The figures are
experimentally derived and expressed relative to the
methane signal (=100).
Note: The results are intended for guidance only. For the
most accurate measurements an instrument should
be calibrated using the gas under investigation.
Gas/Vapour Relative
Sensitivity* Gas/Vapour Relative
Sensitivity*
Methane 100 Carbon monoxide 110
Propane 60 Acetone 65
n-Butane 60 Methyl ethyl ketone 50
n-Pentane 55 Toluene 45
n-Hexane 45 Ethyl acetate 50
n-Heptane 45 Hydrogen 105
n-Octane 40 Ammonia** 125
Methanol 90 Cyclohexane 55
Ethanol 70 Leaded Petrol 55
Iso-propyl alcohol 55 Unleaded petrol 55
Acetylene 80 Ethylene 90
Specifications:
H2S filter lifetime | typically 1000ppm hr |
Output Sensitivity | 28±5 mV/%methane |
T90 Response Time | <20 seconds (methane) |
Linear to | 3% methane |
Long Term Sensitivity Drift | <5% signal/month |
Long Term Zero Drift | <5%LELmethane/month |
Warranty Period | 12 months from date of despatch |
![]() |